Channel Option Menu
Page 12
how the CT was installed and the CT leads polarity. The PT (wall transformer) polarity will also affect
this. It boils down to a 50-50 chance of the polarity being proper.
If the displayed polarity is opposite of what it should be then this function is used to toggle the polarity
to its opposite state. Rather than altering the CT installation or swapping the CT leads, it is much safer
and simpler to correct an improper polarity via this setting. The polarity is displayed when viewing
power under the “Watt menu.
Single Channel Polarity
Figure 7
This function is used to change the polarity of a NET enabled channel if required.
This function is only effective if NET metering is enabled for a given channel. It is used in cases where
the power direction (polarity) is improperly displayed. For example, if channel 1 represents the “main
panel” and the power value displays “negative” when consuming power and “positive” when generating
more power than is being consumed, toggling the channel 1 polarity will change these polarities to
reflect positive for consumed energy and negative for generated.
Effect of the PT on Polarity
It is important to understand that the polarity of the PT will change the polarity of all 32 channels. For
instance, if the wall transformer PT is unplugged turned 180 degrees and re-plugged such that the 120V
receptacle blades are reversed, all channel polarities will change. See Figure 8. This is only an issue for
NET metering enabled channels where polarized values are used.